Generating Set Functional Test Report P015
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12425
CE: NO









RATED OUTPUT
KVA 1500
RATING CLASSIFICATION


PRP


KW 1200






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 2280
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGVM18770
ENGINE MODEL
4012-46TWG4A
SERIAL NUMBER
U11624B
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO 46-1S4
SERIAL NUMBER
0001936075
CONTROL PANEL(S)
DSE 8610
SERIAL NUMBER(S)








SWITCHGEAR
ACB
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
380
912
600



6.3
standby / prime+10% 110% 50.0
380
1970
1296
84/84


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.6
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

22
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

76
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
08.08.2016