Generating Set Functional Test Report U011
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12435
CE: NO









RATED OUTPUT
KVA 15
RATING CLASSIFICATION


PRP


KW 12






PHASE 1






VOLTS 220
PERFORMANCE CLASS

G1


AMPS 68
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GN66044
ENGINE MODEL
404D-22G
SERIAL NUMBER
U965509B
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI144E
SERIAL NUMBER
B16F234817
CONTROL PANEL(S)
7320
SERIAL NUMBER(S)








SWITCHGEAR
A-T-S
SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 80% 50.4
220
44
10



5.0
standby / prime+10% 110% 50.0
220
60
13
82


4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

70









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.4
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

14
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

78
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
30.06.2016