Generating Set Functional Test Report M001A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12335
CE: NO









RATED OUTPUT
KVA 1000
RATING CLASSIFICATION


PRP


KW 800






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 1520
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGBH6127
ENGINE MODEL
4008TAG2A
SERIAL NUMBER
U12055A
ALTERNATOR MAKE
LEROY SOMER


ALTERNATOR MODEL
LSA493L10
SERIAL NUMBER
332319 001
CONTROL PANEL(S)
DSE 7320
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
380
608
400
38


5.8
standby / prime+10% 110% 50.0
380
1337
880
72


4.6









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

98.9
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

10
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

86
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
22.04.2016