Generating Set Functional Test Report S032
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12324
CE: NO









RATED OUTPUT
KVA 9.0
RATING CLASSIFICATION


PRP


KW 7.2






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 13
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GJ66043
ENGINE MODEL
403D-11G
SERIAL NUMBER
U137065V
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO3-2SN/4
SERIAL NUMBER
0001385347
CONTROL PANEL(S)
7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.4
400
8.3
5.8



4.6
standby / prime+10% 110% 50.0
400
11.4
7.9
73


4.0









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

3
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

78
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
17.02.2016