Generating Set Functional Test Report H001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12286
CE: NO









RATED OUTPUT
KVA 150
RATING CLASSIFICATION


PRP


KW 120






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 217
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
PR82148
ENGINE MODEL
1106A-70TAG2
SERIAL NUMBER
U048154Y
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECP34-2L/4
SERIAL NUMBER
0001890373
CONTROL PANEL(S)
COMAP IS-NTC-BB
SERIAL NUMBER(S)
1507EOB








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 50% 50.6
401
87
60



5.1
standby / prime+10% 110% 50.0
400
191
132
82


4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

78
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
07.01.2016