Generating Set Functional Test Report M001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12285
CE: YES









RATED OUTPUT
KVA 24
RATING CLASSIFICATION


PRP


KW 19






PHASE 1






VOLTS 220
PERFORMANCE CLASS

G1


AMPS 109
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DJ32038
ENGINE MODEL
1103A-33G
SERIAL NUMBER
U452591A
ALTERNATOR MAKE
MECCALTE


ALTERNATOR MODEL
ECO32-3S/4
SERIAL NUMBER
0001789309
CONTROL PANEL(S)
7120 MK2
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 90% 50
220
78
17



4.89
standby / prime+10% 110% 50
220
95
21
79


4.55









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

60









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.9
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

10
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

81
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
10.12.2015