Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12276
CE: NO









RATED OUTPUT
KVA 140
RATING CLASSIFICATION


PRP


KW 112






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 194
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
YD51440
ENGINE MODEL
1006TAG
SERIAL NUMBER
U967291Y
ALTERNATOR MAKE
MECCALTE


ALTERNATOR MODEL
ECP34-2L/4
SERIAL NUMBER
0001788108
CONTROL PANEL(S)
7120 MK2
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
415/240
78
56



6.00
standby / prime+10% 110% 50
415/240
171
123
83


4.80









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.4
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

10
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

66
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
17.11.2015