Generating Set Functional Test Report SELECT A CUSTOMER
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12242
CE: YES









RATED OUTPUT
KVA 45
RATING CLASSIFICATION


PRP


KW 36






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 63
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DK32031
ENGINE MODEL
1103A-33TG1
SERIAL NUMBER
U451844A
ALTERNATOR MAKE
MECCALTE


ALTERNATOR MODEL
ECO32-1L/4
SERIAL NUMBER
0001879546
CONTROL PANEL(S)

SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 90% 50
415/240
45
32



5.72
standby / prime+10% 110% 50
415/240
55
40
81


4.61









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

75









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.7
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

9
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

93
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
03.11.2015