Generating Set Functional Test Report C034B
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12188
CE: NO









RATED OUTPUT
KVA 2000
RATING CLASSIFICATION


PRP


KW 1600






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 2783
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
HEAT EXCHANGER









ENGINE MAKE
PERKINS
BUILD NUMBER
DGBR6258
ENGINE MODEL
4016-TAG2A
SERIAL NUMBER
U10827A
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734F
SERIAL NUMBER
A15I377154
CONTROL PANEL(S)
8610
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 57% 50.0
415
1269
912



6.1
standby / prime+10% 110% 50.0
415
2449
1760
78


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

75
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
30.10.2015