Generating Set Functional Test Report A074
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12236
CE: NO









RATED OUTPUT
KVA 1700
RATING CLASSIFICATION


PRP


KW 1360






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 2583
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDM6064
ENGINE MODEL
4012-46TAG3A
SERIAL NUMBER
U12416X
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734E
SERIAL NUMBER
0274369/008
CONTROL PANEL(S)
7320
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 63% 50.0
380
1302
857



5.3
standby / prime+10% 110% 50.0
380
2273
1496
72


4.6









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

83
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
29.10.2015