Generating Set Functional Test Report P006 | ||||||||
In accordance with ISO 8528 - 6 2005 | ||||||||
PLANT NUMBER: |
E
12235 |
CE: | NO | |||||
RATED OUTPUT | KVA |
100 |
RATING CLASSIFICATION |
PRP |
||||
KW |
80 |
|||||||
PHASE |
3 |
|||||||
VOLTS |
400/230 |
PERFORMANCE CLASS |
G1 | |||||
AMPS |
144 |
(AS DEFINED BY ISO 8528-1) |
||||||
HZ |
50 |
|||||||
RPM |
1500 |
|||||||
GOVERNOR TYPE |
ELECTRONIC |
COOLING METHOD | LIQUID |
|||||
ENGINE MAKE |
PERKINS |
BUILD NUMBER |
RJ51175 | |||||
ENGINE MODEL |
1104C-44TAG2 |
SERIAL NUMBER |
U604280Y | |||||
ALTERNATOR MAKE |
MECCALTE |
|||||||
ALTERNATOR MODEL |
ECP342S |
SERIAL NUMBER |
0001860877 | |||||
CONTROL PANEL(S) |
|
SERIAL NUMBER(S) |
||||||
SWITCHGEAR |
|
SERIAL NUMBER(S) |
||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | 75% |
50 |
400/230 |
87 |
60 |
|
|
5.86 |
standby / prime+10% | 110% |
50 |
400/230 |
127 |
88 |
85 |
|
3.99 |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
|
||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) |
99.7 |
DENSITY | 0.84 kg/l | |||||
TEMPERATURE (Deg c) |
17 |
CALORIFIC VALUE |
42.5 MJ/kg | |||||
HUMIDITY (%) |
93 |
LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE |
|
CONTROL PANEL(S) |
||||||
TESTED BY | ![]() |
DATE | 06.10.2015 |