Generating Set Functional Test Report C034A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12209
CE: NO









RATED OUTPUT
KVA 15
RATING CLASSIFICATION


PRP


KW 15






PHASE 1






VOLTS 230
PERFORMANCE CLASS

G1


AMPS 65
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GV51790
ENGINE MODEL
404A-22G1
SERIAL NUMBER
U949775A
ALTERNATOR MAKE
MECCALTE


ALTERNATOR MODEL
ECP28-VL/4
SERIAL NUMBER
0001843258
CONTROL PANEL(S)
7120MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 80% 50
230
52
12



5.17
standby / prime+10% 110% 50
230
72
17
84


4.13









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.7
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

11
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

86
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
24.09.2015