Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12189
CE: NO









RATED OUTPUT
KVA 500
RATING CLASSIFICATION


ESP


KW 400






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 696
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
MGAF5125
ENGINE MODEL
2506A-E15TAG1
SERIAL NUMBER
N01507A
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI544D
SERIAL NUMBER
A15H321347
CONTROL PANEL(S)
DSE 7310
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
415
334
240
32


5.6
standby / prime+10% 100% 50.0
415
557
400
89


4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.6
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

14
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

78
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
08.09.2015