Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12182
CE: NO









RATED OUTPUT
KVA 160
RATING CLASSIFICATION


PRP


KW 128






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 243
(AS DEFINED BY ISO 8528-1)




HZ 60.0






RPM 1800




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
PR82217
ENGINE MODEL
1106A-70TAG2
SERIAL NUMBER
U050699A
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274E
SERIAL NUMBER
A15H333272
CONTROL PANEL(S)
7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 75% 60.5
380
146
96



6.1
standby / prime+10% 110% 60.0
380
214
141
83


4.7









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

12
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

74
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
04.09.2015