Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12154
CE: NO









RATED OUTPUT
KVA 750
RATING CLASSIFICATION


PRP


KW 600






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 1043
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGBF6118
ENGINE MODEL
4006-23TAG2A
SERIAL NUMBER
U11780A
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO40-VL/4
SERIAL NUMBER
0001868558
CONTROL PANEL(S)
7310
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 69% 50.0
415
576
414



5.4
standby / prime+10% 110% 50.0
415
918
660
72


4.5









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.8
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

18
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

83
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
21.08.2015