Generating Set Functional Test Report G012
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12177
CE: NO









RATED OUTPUT
KVA 400
RATING CLASSIFICATION


PRP


KW 320






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 557
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
TGDF5018
ENGINE MODEL
2206A-E13TAG3
SERIAL NUMBER
N01286A
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI44F
SERIAL NUMBER
A14J442810
CONTROL PANEL(S)
DSE 7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
223
160
24


4.3
standby / prime+10% 110% 50.0
400
490
352
88


3.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

85









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.5
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

22
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

56
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
12.08.2015