Generating Set Functional Test Report S032
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12147
CE: NO









RATED OUTPUT
KVA 13
RATING CLASSIFICATION


PRP


KW 10.4






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 19
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GV51798
ENGINE MODEL
403A-15G1
SERIAL NUMBER
U553209Y
ALTERNATOR MAKE
MECCALTE


ALTERNATOR MODEL
ECP280S4
SERIAL NUMBER
0001775519
CONTROL PANEL(S)

SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 80% 50
400/230
12
8.3



5.17
standby / prime+10% 110% 50
400/230
17
11.4
82


4.61









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

102.5
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

23
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

56
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
03.07.2015