Generating Set Functional Test Report S064
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12094
CE: NO









RATED OUTPUT
KVA 1650
RATING CLASSIFICATION


PRP


KW 1320






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 2384
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDM6064
ENGINE MODEL
4012-46TAG3A
SERIAL NUMBER
U10524W
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI734D
SERIAL NUMBER
A13G287870
CONTROL PANEL(S)
TBOX
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
867
660



5.4
standby / prime+10% 110% 50.0
400
1908
1452
72


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.1
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

20
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

73
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
01.07.2015