Generating Set Functional Test Report M001A | ||||||||
In accordance with ISO 8528 - 6 2005 | ||||||||
PLANT NUMBER: |
E
12121 |
CE: | NO | |||||
RATED OUTPUT | KVA |
250 |
RATING CLASSIFICATION |
PRP |
||||
KW |
200 |
|||||||
PHASE |
3 |
|||||||
VOLTS |
380/220 |
PERFORMANCE CLASS |
G1 | |||||
AMPS |
380 |
(AS DEFINED BY ISO 8528-1) |
||||||
HZ |
50 |
|||||||
RPM |
1500 |
|||||||
GOVERNOR TYPE |
ECU |
COOLING METHOD | LIQUID |
|||||
ENGINE MAKE |
PERKINS |
BUILD NUMBER |
WGHF7204 | |||||
ENGINE MODEL |
1306C-E87TAG6 |
SERIAL NUMBER |
N10687A | |||||
ALTERNATOR MAKE |
STAMFORD |
|||||||
ALTERNATOR MODEL |
UCD274K |
SERIAL NUMBER |
A14D155734 | |||||
CONTROL PANEL(S) |
DSE 7120 MKII |
SERIAL NUMBER(S) |
||||||
SWITCHGEAR |
|
SERIAL NUMBER(S) |
||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % |
50.0 |
400 |
109 |
72 |
|
|
4.6 |
standby / prime+10% | 110% |
50.0 |
400 |
334 |
220 |
91 |
|
3.3 |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
|
||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) |
101.7 |
DENSITY | 0.84 kg/l | |||||
TEMPERATURE (Deg c) |
20 |
CALORIFIC VALUE |
42.5 MJ/kg | |||||
HUMIDITY (%) |
79 |
LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE |
|
CONTROL PANEL(S) |
||||||
TESTED BY | ![]() |
DATE | 17.06.2015 |