Generating Set Functional Test Report M001A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12121
CE: NO









RATED OUTPUT
KVA 250
RATING CLASSIFICATION


PRP


KW 200






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 380
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ECU
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
WGHF7204
ENGINE MODEL
1306C-E87TAG6
SERIAL NUMBER
N10688A
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCD274K
SERIAL NUMBER
A14E210149
CONTROL PANEL(S)
DSE 7120 MKII
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
109
72



4.5
standby / prime+10% 110% 50.0
400
334
220
88


3.6









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.7
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

20
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

79
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
17.06.2015