Generating Set Functional Test Report M001
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12108
CE: NO









RATED OUTPUT
KVA 63
RATING CLASSIFICATION


ESP


KW 50.4






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 91
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DK51436
ENGINE MODEL
1103A-33TG2
SERIAL NUMBER
U418743Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI224E
SERIAL NUMBER
A14I399303
CONTROL PANEL(S)
DSE 7210
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.0
400
58
40



5.3
standby / prime+10% 110% 50.0
400
80
55
82


4.3









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

103.5
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

15
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

63
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
09.06.2015