Generating Set Functional Test Report C034A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12090
CE: NO









RATED OUTPUT
KVA 15
RATING CLASSIFICATION


PRP


KW 12






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 22
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
GU51794
ENGINE MODEL
403A-15G2
SERIAL NUMBER
U565453Y
ALTERNATOR MAKE
MECCALTE


ALTERNATOR MODEL
ECP28-S4
SERIAL NUMBER
0001847478
CONTROL PANEL(S)
7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50
400/230
14
9.6



4.27
standby / prime+10% 110% 50
400/230
25
18
83


3.58









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

103.6
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

11
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

78
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
09.06.2015