Generating Set Functional Test Report P015
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12070
CE: NO









RATED OUTPUT
KVA 140
RATING CLASSIFICATION


PRP


KW 112






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 202
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
YD51440
ENGINE MODEL
1006TAG
SERIAL NUMBER
U967566Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
UCI274E
SERIAL NUMBER
A15B098149
CONTROL PANEL(S)
DSE 7110
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.9
400
105
73



5.4
standby / prime+10% 110% 50.0
400
178
123
81


4.2









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

13
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

75
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
08.05.2015