Generating Set Functional Test Report M054
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 12067
CE: NO









RATED OUTPUT
KVA 800
RATING CLASSIFICATION


PRP


KW 640






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 1216
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE ELECTRONIC
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DGDF6116
ENGINE MODEL
4006-23TAG3A
SERIAL NUMBER
U17769X
ALTERNATOR MAKE
MECC-ALTE


ALTERNATOR MODEL
ECO43-1SN/4
SERIAL NUMBER
0001808933
CONTROL PANEL(S)
7220
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 50.0
380
584
384



5.8
standby / prime+10% 110% 50.0
380
1070
704
70


5.1









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

101.4
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

7
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

57
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
27.04.2015