Generating Set Functional Test Report U011
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11967
CE: NO









RATED OUTPUT
KVA 40
RATING CLASSIFICATION


PRP


KW 32






PHASE 3






VOLTS 400/230
PERFORMANCE CLASS

G1


AMPS 55
(AS DEFINED BY ISO 8528-1)




HZ 50






RPM 1500




GOVERNOR TYPE MECHANICAL
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
DK32031
ENGINE MODEL
1103A-33TG1
SERIAL NUMBER
U421701Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
PI144J
SERIAL NUMBER
B11L509233
CONTROL PANEL(S)
DSE 7120
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance % 50.9
415
45
32



5.3
standby / prime+10% 110% 50.0
415
49
35
80


4.4









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP

75









AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

97.3
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

0
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

93
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
29.01.2015