Generating Set Functional Test Report M001A
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11919
CE: NO









RATED OUTPUT
KVA 300
RATING CLASSIFICATION


PRP


KW 240






PHASE 3






VOLTS 380/220
PERFORMANCE CLASS

G1


AMPS 456
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE E.C.M.
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
LGFF0001
ENGINE MODEL
1506A-E88TAG5
SERIAL NUMBER
N00115Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI444D
SERIAL NUMBER
A14F231766
CONTROL PANEL(S)
7220
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 50.0
380
219
144



6.0
standby / prime+10% 110% 50.0
380
401
264
88


3.6









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.2
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

4
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

87
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
20.01.2015