Generating Set Functional Test Report SELECT A CUSTOMER | ||||||||
In accordance with ISO 8528 - 6 2005 | ||||||||
PLANT NUMBER: |
E
11929 |
CE: | NO | |||||
RATED OUTPUT | KVA |
60 |
RATING CLASSIFICATION |
PRP |
||||
KW |
48 |
|||||||
PHASE |
3 |
|||||||
VOLTS |
380 |
PERFORMANCE CLASS |
G1 | |||||
AMPS |
91 |
(AS DEFINED BY ISO 8528-1) |
||||||
HZ |
50 |
|||||||
RPM |
1500 |
|||||||
GOVERNOR TYPE |
MECHANICAL |
COOLING METHOD | LIQUID |
|||||
ENGINE MAKE |
PERKINS |
BUILD NUMBER |
DK51280 | |||||
ENGINE MODEL |
1103A-33TG2 |
SERIAL NUMBER |
U416916Y | |||||
ALTERNATOR MAKE |
MECC-ALTE |
|||||||
ALTERNATOR MODEL |
ECO32-2L/4 |
SERIAL NUMBER |
0001805144 | |||||
CONTROL PANEL(S) |
DSE7120MKII |
SERIAL NUMBER(S) |
||||||
SWITCHGEAR |
|
SERIAL NUMBER(S) |
||||||
LOAD TEST RESULTS (AT UNITY POWER FACTOR) | ||||||||
LOAD | HZ | VOLTS | AMPS | KW | ENGINE | OIL | OIL | |
type | % | TEMP | TEMP | PRESS | ||||
DEG C | DEG C | BAR | ||||||
load acceptance | % |
50 |
380 |
58 |
40 |
- |
- |
5.05 |
standby / prime+10% | 110% |
50 |
380 |
80 |
52 |
80 |
- |
4.32 |
GENERATING SET ENCLOSURE MECHANICAL PROTECTION AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M) (UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD IN ACCORDANCE WITH ISO8528-10) |
IP | |||||||
|
||||||||
AMBIENT TEST CONDITIONS | FUEL/OIL USED | |||||||
ALTITUDE (M) | Sea Level | FUEL SPEC | BS2869A2 | |||||
BAROMETRIC PRESSURE (kpa) |
|
DENSITY | 0.84 kg/l | |||||
TEMPERATURE (Deg c) |
|
CALORIFIC VALUE |
42.5 MJ/kg | |||||
HUMIDITY (%) |
|
LUB OIL SPEC | Multigrade | |||||
WIRING DIAGRAMS: | ||||||||
ENGINE |
|
CONTROL PANEL(S) |
||||||
TESTED BY | ![]() |
DATE | 22.12.2014 |