Generating Set Functional Test Report P006
In accordance with ISO 8528 - 6 2005









PLANT NUMBER:
E 11962
CE: NO









RATED OUTPUT
KVA 350
RATING CLASSIFICATION


PRP


KW 280






PHASE 3






VOLTS 415/240
PERFORMANCE CLASS

G1


AMPS 487
(AS DEFINED BY ISO 8528-1)




HZ 50.0






RPM 1500




GOVERNOR TYPE E.C.M.
COOLING METHOD
LIQUID









ENGINE MAKE
PERKINS
BUILD NUMBER
TGBF5112
ENGINE MODEL
2206A-E13TAG2
SERIAL NUMBER
U18734Y
ALTERNATOR MAKE
STAMFORD


ALTERNATOR MODEL
HCI444E
SERIAL NUMBER
A12K480007
CONTROL PANEL(S)
7310
SERIAL NUMBER(S)








SWITCHGEAR

SERIAL NUMBER(S)
















LOAD TEST RESULTS (AT UNITY POWER FACTOR)
LOAD HZ VOLTS AMPS KW ENGINE OIL OIL
type %



TEMP TEMP PRESS






DEG C DEG C BAR
load acceptance 60% 50.0
415
234
168



4.6
standby / prime+10% 110% 50.0
415
429
308
88


2.9









GENERATING SET ENCLOSURE MECHANICAL PROTECTION
AVERAGE SOUND PRESSURE LEVEL (DBA AT 1 M)
(UNITS WITH ACOUSTIC CANOPIES ONLY & MEASURED UNDER TEST BAY CONDITIONS AT 75% LOAD
IN ACCORDANCE WITH ISO8528-10)

IP











AMBIENT TEST CONDITIONS FUEL/OIL USED
ALTITUDE (M)

Sea Level FUEL SPEC
BS2869A2
BAROMETRIC PRESSURE (kpa)

100.8
DENSITY
0.84 kg/l
TEMPERATURE (Deg c)

8
CALORIFIC VALUE
42.5 MJ/kg
HUMIDITY (%)

80
LUB OIL SPEC
Multigrade









WIRING DIAGRAMS:
ENGINE
CONTROL PANEL(S)
















TESTED BY




DATE
19.12.2014